doc_recs4:software_interface [2022/02/17 14:40] vordoc_recs4:software_interface [2022/02/28 08:37] bil
Line 205: Line 205:
 Example XML: Example XML:
  
-<code xml><rcu rcuType="ANTARES" fanSpeed="60" rackId="RCK_1" name="RECSMaster (RCU) on 192.168.56.195" rackPosition="0" id="RCU_84055620466592" lastSensorUpdate="1465470151268">+<code xml><rcu rcuType="ANTARES" fanSpeed="60" fanProfile="adjust_by_temperature" rackId="RCK_1" name="RECSMaster (RCU) on 192.168.56.195" rackPosition="0" id="RCU_84055620466592" lastSensorUpdate="1465470151268">
 <backplaneId>RCU_84055620466592_BP_1</backplaneId> <backplaneId>RCU_84055620466592_BP_1</backplaneId>
 <baseboardId>RCU_84055620466592_BB_1</baseboardId> <baseboardId>RCU_84055620466592_BB_1</baseboardId>
Line 226: Line 226:
 |''kvmNode'' |ID of the node to which the KVM system is switched (optional)|-|String| |''kvmNode'' |ID of the node to which the KVM system is switched (optional)|-|String|
 |''fanSpeed'' |Current speed setting of the fans in the RECS<sup>(r)</sup>%%|%%Box Computing Unit|%|Integer| |''fanSpeed'' |Current speed setting of the fans in the RECS<sup>(r)</sup>%%|%%Box Computing Unit|%|Integer|
 +|''fanProfile'' |Current fan profileof the RECS<sup>(r)</sup>%%|%%Box Computing Unit|%|Integer|
 |''lastSensorUpdate'' |Timestamp of the last sensor update|ms|Long| |''lastSensorUpdate'' |Timestamp of the last sensor update|ms|Long|
 |''backplaneId'' |List of ID****s of backplanes which are installed in the RECS<sup>(r)</sup>%%|%%Box Computing Unit|-|String| |''backplaneId'' |List of ID****s of backplanes which are installed in the RECS<sup>(r)</sup>%%|%%Box Computing Unit|-|String|
Line 284: Line 285:
 |''/node/{node_id}/manage/select_kvm'' |Switches the KVM port of the RECS<sup>(r)</sup>%%|%%Box Computing Unit containing the node to the node with the given ID and returns updated node XML|PUT| | |''/node/{node_id}/manage/select_kvm'' |Switches the KVM port of the RECS<sup>(r)</sup>%%|%%Box Computing Unit containing the node to the node with the given ID and returns updated node XML|PUT| |
 |''/rcu/{rcu_id}/manage/set_fans'' |Sets the overall fan speed of the RCU with the given ID and returns the curent status of the RCU|PUT|percent={value}| |''/rcu/{rcu_id}/manage/set_fans'' |Sets the overall fan speed of the RCU with the given ID and returns the curent status of the RCU|PUT|percent={value}|
 +|''/rcu/{rcu_id}/manage/set_fan_profile'' |Sets the fan profile of the RCU with the given ID and returns the curent status of the RCU (Possible values: manual, increase_by_temperature, adjust_by_temperature)|PUT|percent={value}|
  
 === Errors === === Errors ===
Line 313: Line 315:
  
 It is recommended to use Grafana as a graphical dashboard to read out these captured metrics. A pre-build Grafana dashboard is publicly available at https://grafana.com/grafana/dashboards/14622. It can be integrated in Grafana using the "Import" function. It automatically reads the available metrics from the database and dynamically adapts to the number of available microservers, see the following picture: It is recommended to use Grafana as a graphical dashboard to read out these captured metrics. A pre-build Grafana dashboard is publicly available at https://grafana.com/grafana/dashboards/14622. It can be integrated in Grafana using the "Import" function. It automatically reads the available metrics from the database and dynamically adapts to the number of available microservers, see the following picture:
 +
 +<imgcaption web-gui-overview|>
 +{{ :documentation:grafana.png?direct |Grafana Dashboard}}</imgcaption>
 +